Superior SeismoProtect G3 Fibra

Wired seismic detector with an additional shock sensor

FAQ

The siren has a sealed battery that powers the device. The battery charges from the Fibra line and is used both for indication and for notifying about alarms and events.

If the Fibra line is damaged or there’s an emergency power shortage, the backup battery will provide the siren with power to indicate and alert alarms and events.

In the Ajax apps, you can set the siren to activate an alarm if the Fibra line is damaged.

Copied

Terminating resistor is a consistent load for a long line. It is required to avoid the influence of the signal reflected from the end of the line. A 120 Ohm terminating resistor is included in the complete set of a hub.

A terminating resistor is installed between signal terminals of the last device in the line created using the Beam topology.

With the Ring topology, a terminating resistor is not needed.

Copied

In the states of each Fibra device, you can see its loop (zone) number as well as number of the line to which it is connected. When using the Ring topology, you can see to which ring the device is connected.

If the device is added to the hub, for example, using LineSupply (75 W) Fibra, you can see the module name and the output line number in the states.

Copied

The lines power test shows which devices and on which Fibra lines may have insufficient power supply.

If the power supply is insufficient, we cannot guarantee the stable operation of the security system.

Before installing wired devices, we recommend calculating the line length using an online calculator.

If a certain device is not getting enough power supply, you can:

  • Add devices to the hub through the LineSupply Fibra module.
  • Connect devices that are not powered enough to another Fibra line.
  • Reduce the number of devices on the Fibra line that is not powered enough.
  • Replace high-power consuming devices with lower-power devices if facility configuration allows.

After any change in the device configuration at the facility, we recommend re-testing the lines power supply.

Copied

When installing Fibra devices, be sure to observe the polarity and order of the wires connected.

Copied

When installing devices near power cables, we recommend using a shielded cable to lay the Fibra wired line.

Copied

Fibra devices work on 24V⎓ voltage.

The minimum allowable voltage for Fibra devices to operate is 8 V⎓. Such a voltage may be at the end of a line to which many devices are connected.

If the voltage on a device is below 8V⎓, a fault counter will appear on that device, and the Voltage field in the device States will turn to red color.

Thus, we recommend that you perform a Lines Power Test after installing the devices to ensure that they work correctly.

Copied

Ajax security system provides several tests to check the operation of wired devices.

Fibra Signal Strength Test checks the device signal strength and stability at the intended installation location.

Detection Zone Test checks how the device responds to alarms (the test is only available for Ajax security detectors).

Volume Level Test — checks the siren volume sound at the intended installation location (the test is only available for Ajax sirens).

Lines Power Test simulates the maximum possible power consumption of the system: detectors generate alarms, keypads are activated, sirens are turned on. If the system successfully passed the test, then all its wired devices will have enough power supply in any situation.

During the lines power test, connected wired sirens are activated.

We recommend that you perform all security system tests after installing the devices to ensure that they work correctly.

Copied

Fibra devices are connected to the hub using Beam (Radial wiring), Ring, and Tree topologies.

As depicted in the diagram, wired devices should be connected to the Fibra line sequentially, one after the other, without any branching.

Line branching and the Tree topology are only allowed when using LineSplit Fibra.

The Ring topology is also available. If the line breaks, the devices will still be connected to the hub via the Beam (Radial wiring) connection, continuing to transmit events and alarms to the hub.

We recommend connecting devices using the Ring topology if possible. This improves the sabotage protection of the line.

Keep in mind, the output lines created when using LineSplit Fibra or LineProtect Fibra don’t support the Ring topology.

Learn more

Copied

The maximum length of a wired Fibra line is 2,000 meters.

The appropriate wired line length depends on the number and type of connected devices and the type of used cable.

Therefore, before installing wired devices, we recommend calculating the line length using an online calculator.

And after installing the devices, perform a Fibra Signal Strength Test and a Lines Power Test to make sure the system is working correctly.

Copied

Fibra devices are connected using a 4-wire cable.

We recommend using the following types of conductors:

  • U/UTP cat.5 twisted pair (4 × 2 × 0.51).
  • ALARM signal cable (4 × 0.22).
Copied

Spelling error report

The following text will be sent to our editors: